To receive competitive purchasing options on part number CM-21A by 3M Company, look no further than NSN Direct. For your reference, this item has the NSN 6665-01-530-2725 and is listed with the description “Alarm Gas Automatic.” If this matches your needs, we encourage you to fill out the partially-completed quote request form on this page to kick off procurement. By providing comprehensive information about your requirements, such as your desired quantity, pricing, and fulfillment speed, our experts can formulate the most fitting solutions for you. We want to ensure that this process is quick and effortless, so we routinely respond to requests within 15 minutes of receiving and reviewing them.
Note : We Will Not Share Your Information To Any Third Parties.
In addition to our streamlined quotation service, we also aim to make the process of finding products simple. As such, if you require other 3M Company parts produced under the CAGE Code 76381, you can peruse our manufacturer or CAGE Code catalogs, or use our search engine and filters. Furthermore, if you want to locate items similar to part number CM-21A, you can glean from the first four digits of its NSN 6665-01-530-2725 that it belongs to the FSC 6665 Hazard Detecting Instruments And Apparatus. This being said, do not hesitate to request quotes on part number CM-21A and any other NSN parts that we feature to experience unrivaled procurement.
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |