To receive competitive purchasing options on part number TFJ236225 by General Electric Company, look no further than NSN Direct. For your reference, this item has the NSN 5925-00-728-9610 and is listed with the description “Circuitbreaker.” If this matches your needs, we encourage you to fill out the partially-completed quote request form on this page to kick off procurement. By providing comprehensive information about your requirements, such as your desired quantity, pricing, and fulfillment speed, our experts can formulate the most fitting solutions for you. We want to ensure that this process is quick and effortless, so we routinely respond to requests within 15 minutes of receiving and reviewing them.
Note : We Will Not Share Your Information To Any Third Parties.
In addition to our streamlined quotation service, we also aim to make the process of finding products simple. As such, if you require other General Electric Company parts produced under the CAGE Code 60969, you can peruse our manufacturer or CAGE Code catalogs, or use our search engine and filters. Furthermore, if you want to locate items similar to part number TFJ236225, you can glean from the first four digits of its NSN 5925-00-728-9610 that it belongs to the FSC 5925 Circuit Breakers. This being said, do not hesitate to request quotes on part number TFJ236225 and any other NSN parts that we feature to experience unrivaled procurement.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-728-9610 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007289610 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
TFJ236225 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 10.125 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.188 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.375 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.750 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 225.0 AMPERES AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 9.000 MAXIMUM AT 100 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 22000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |