To receive competitive purchasing options on part number PS-2-2457-5 by Navair And Navsea Managed, look no further than NSN Direct. For your reference, this item has the NSN 5925-00-075-7892 and is listed with the description “Circuit Breaker.” If this matches your needs, we encourage you to fill out the partially-completed quote request form on this page to kick off procurement. By providing comprehensive information about your requirements, such as your desired quantity, pricing, and fulfillment speed, our experts can formulate the most fitting solutions for you. We want to ensure that this process is quick and effortless, so we routinely respond to requests within 15 minutes of receiving and reviewing them.
Note : We Will Not Share Your Information To Any Third Parties.
In addition to our streamlined quotation service, we also aim to make the process of finding products simple. As such, if you require other Navair And Navsea Managed parts produced under the CAGE Code 10001, you can peruse our manufacturer or CAGE Code catalogs, or use our search engine and filters. Furthermore, if you want to locate items similar to part number PS-2-2457-5, you can glean from the first four digits of its NSN 5925-00-075-7892 that it belongs to the FSC 5925 Circuit Breakers. This being said, do not hesitate to request quotes on part number PS-2-2457-5 and any other NSN parts that we feature to experience unrivaled procurement.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-075-7892 Item Description: Circuit Breaker | 5925 | 000757892 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Ps-2-2457-5 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
CQXF | Inclosure Protection Type For Which Designed | EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.062 INCHES NOMINAL |
AAQL | Body Style | SINGLE POLE TYPE |
MRC | Decoded Requirement | Clear Text Reply |
CPLM | Maximum Continuous Load Current Rating Per Pole | 5.0 AMPERES AC SINGLE LOCATION |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC SINGLE LOCATION |
CPRH | Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC SINGLE LOCATION |
FREQ | Frequency In Hertz | 60.0 SINGLE LOCATION |
AXHR | Mounting Facility Type And Quantity | 2 THREADED HOLE |
AKPX | Pole Quantity | 1 |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 SINGLE LOCATION |
ADAT | Body Width | 0.750 INCHES NOMINAL |
CPRL | Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
CPRQ | Reset Method | MANUAL |
AJEC | Boss Height | 0.125 INCHES NOMINAL |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRW | Actuator Function | TRIP-RESET |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
CPSM | Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
THSD | Thread Series Designator | UNF |
CQJX | Nominal Thread Size | 0.190 INCHES |
TTQY | Terminal Type And Quantity | 2 THREADED STUD |
AJWX | Mounting Surface To Terminal End Distance | 1.359 INCHES NOMINAL |
ADTV | Case Material | PLASTIC |
ADAQ | Body Length | 2.500 INCHES NOMINAL |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.938 INCHES NOMINAL |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC SINGLE LOCATION |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 75.000 NOMINAL AT 100 PCT SINGLE LOCATION AND 10.000 MINIMUM AT 125 PCT SINGLE LOCATION AND 75.000 MAXIMUM AT 125 PCT SINGLE LOCATION AND 5.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 9.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.700 MINIMUM AT 400 PCT SINGLE LOCATION AND 2.000 MAXIMUM AT 400 PCT SINGLE LOCATION AND 0.500 MINIMUM AT 500 PCT SINGLE LOCATION AND 1.000 MAXIMUM AT 500 PCT SINGLE LOCATION |
CMLP | Thread Quantity Per Inch | 32 |
CPRP | Ultimate Trip Time Per Pole In Seconds | 10.000 MINIMUM SINGLE LOCATION AND 75.000 MAXIMUM SINGLE LOCATION |
CPRX | Actuator Position Designation | BETWEEN POLE ONE AND TWO |